Location
The SafeData hosted solution is located in the Greenwich data centre in East London. This data centre is ideal for out of Docklands co-location with direct links to central London and provides excellent pricing for standard power co-location.
The site also benefits from having completely diverse data rooms onsite with diverse power feeds from the grid, UPS, switch gear and AC. This provides the ideal solution for diverse multiple collocation racks in the same facility.
The facility has the added benefits of being connected to our Data centre provisioning partner thus allowing us to grow our cloud facility by being connected to all major data centres across the UK and the Europe. The facility is on a separate power grid to Docklands and Telehouse, making this an excellent failover site.
Technology
We have partnered with leading system manufacturers for the hardware we use and trust to operate SafeData on. Our partners include Intel, HP, Cisco and Microsoft. We operate a dual hardware appliance environment to ensure a complete failover redundancy. Our facilities allow over 280TB of storage space per full height rack and we have guaranteed availability to grow our storage server systems to well over 1 Petabyte.
Power
• 2 x 1.0mva dedicated power supply. One supply per server room
• Dual 16-32a commando sockets via dedicated radial SWA cables via “A” and “B” CPDU per server hall
• 22 x 500kva synchronised (N+N) Emerson HiPulse “E” range, Double conversion static UPS, per server room
• Each UPS to have a 5-string set of 10 year life batteries, providing minutes autonomy
• 5 x 500kva Diesel Generators (N+1) Parallel synchronised to feed the entire site
• Air cooled, Turbo charged Volvo, Electronic governor, Marelli alternator
• Close fitting acoustic enclosure and integral 8 hr “day” tank
Air-Conditioning
• 8 x 80kw, DX (R407), Full Function, Downflow, CRAC units server room (N+1)
• UPS room cooling load 600Kw – 2 x 80Kw DX, Upflow, CRAC units (N+N)
• Room condition -23 0C, 45% RH
Fire Protection & Security
• New independent smoke detection systems to the plant room and each server room
• VESDA in the plant room, server rooms
• Plant room and server rooms each links to its own Argonite gas suppression system
• General areas and offices on main building smoke detection system
• Multizone panel with sensing tape per server room, and in Plant and Meet Me rooms
• PAC card access to the main entrance, and ancillary areas
• Palm readers to server room doors
• 24 x 7 Manned Security
• CCTV on main entrance, loading bay server rooms and plant room
• Motorised Dome, Low light level, CCTV camera to the external provider